Anhui Xuneng control engineering Co., Ltd
CONTACT US
Address:401 Quality Inspection Building, south of Fanhua Avenue and west of Jixian Road, Economic and Technological Development Zone, Hefei City, Anhui Province
Telephone:+86-551-65709580
Fax:+86-551-63540585
E-mail:info@xncontrol.com
Your current location:Home > Products Flame detection system
Integrated intelligent infrared flame detector
Time:2018-04-15 16:32:46

Introduce:

Integrated intelligent infrared flame detector is a fully integrated optical intelligent flame detection device, which adopts advanced digital signal processor, high sensitivity spectral sensor, and integrates advanced fire watching algorithm. It is used to detect flames of fuels such as coal powder, fuel oil, and gas. Suitable for flame detection of multi fuel burners and single fuel burners.

By detecting the radiation signal in the flame stable combustion zone, analyzing the vibration amplitude (flame flicker) generated by the target flame, and capturing the optimal ON/OFF resolution of flame vibration frequency, output ON/OFF contact signal, 4-20MA flame intensity signal, and alarm signal.

Based on an integrated design, the detector consists of sensors and signal processing units, eliminating the need for separate signal amplifier boards, reducing equipment failure points and maintenance workload. The output signal of the detector is stable and cost-effective.

Realize on-site LED status display and control, and the internal parameters of the detector are simple to set, making maintenance and use very convenient.


Technical parameter:

SensingDeviceType:IR: InGaAs  

Shell material:aluminum material

Weight:0.9kg

Protection grade:IP66

Cooling air flow rate:17m3/hr

Cooling air pressure:6Kpa

Sensor spectral range:IR:900nm~1700nm

Input power supply:24VDC±15%,0.2A

work environment:-40°~+85°

Humidity range: 0% -95% relative humidity, non condensing

Output contact type: Flame signal: dry contact, SPST (normally open) Alarm signal: dry contact, SPST (normally closed) 

Output contact capacity:2A@30VDC/2A@240VAC

Analog signal output: 4-20mA DC, active output, maximum connected load: 750 Ω


Boiler flame detector, site installation picture